English

Espanol

Japanese

Korean

Montreal-Apartments Montreal-student-Info Montreal-Short-term-stays Montreal_real-Estate-Contest Federal-Real-Estate-client Federal-Real-Estate-Contact Federal-Real-Estate-Home
Home > Montreal Student Information > Maintenance Information > Appliance Tips
> back to index
> translate this page

Air Conditioner Unit Maintenance

Compressor does not start (no hum)

Cause Solution
Start switch is open or defective
Fuse removed or blown
Control stuck in open position
Control off due to cold location
Loose or incorrect wiring
Internal overload opening
Close or replace switch.
Replace fuse.
Repair or replace control.
Relocate control.
Check wiring diagram and correct.
Allow compressor to cool.

Compressor will not start (hums but trips the line-break motor protector)

Cause Solution
Incorrectly wired
Low voltage to unit
Relay defective, burned out, or failing to close
Liquid refrigerant in compressor
Compressor motor winding open or shorted
Internal mechanical trouble in compressor
Check diagram and correct wiring accordingly.
Determine reason for low voltage and correct. 
Check "relay defective" section, burned out….. 
Add crank case heater. 
Replace compressor.
Replace compressor.

Compressor starts but short-cycles on internal load

Cause Solution
Excess current passing through line-break motor protector
Low voltage to unit
Run capacitor defective (PSC type motor only)
High system pressure
Low system pressure
Compressor overheated
Compressor motor winding shorted
Internal overload defective
Read section "excess current……"
Determine reason for low voltage.
Discussed later in section "Run capacitor…."
Discussed later in section "High system…."
Discussed later in section "Low system…." 
Discussed later in section " Compressor overheated."
Replace compressor.
Replace compressor.

Compressor starts but thermostat short cycles

Cause Solution
Thermostat differential set too closely Adjust thermostat differential. (check manual)

Compressor operates too long continuously

Cause Solution
System undercharged
Control contacts stuck or frozen
Air-conditioned space has excessive load or poor insulation
System inadequate to handle load
Evaporator coil iced
Restricted in refrigeration system
Dirty condensing unit
Dirty filter
Repair leaks in system, if needed.
Check system charge requirements and adjust accordingly.
Clean contacts or replace control.
Determine problem and correct.
Replace with larger system.
Defrost coil. Find and remove restriction.
Clean condensing unit.
Clean or replace filter.

Compressor Overheated

Cause Solution
System undercharged
System leaking
Charge system.
Check entire system, repair leak, and charge system.

Excess current through line-break motor protector

Cause Solution
Compressor system components incorrectly wired
Additional electrical equipment in stalled ins systems electrical circuit
Correct wiring.
Check capacity of system's electrical circuit. Rewiring (dividing) circuit may be needed.
Start capacitor open, shorted, or blown (If applicable; for PSC type motor only)

Cause Solution
Relay contact not operating properly
Prolonged operation on start cycle due to low voltage to unit, wrong relay, or refrigeration system starting load too high.
Excessive short-cycling
Wrong start capacitor
Clean contacts or replace relay.
Determine reason for low voltage and correct; replace relay, or adjust system pressure.
Determine reason and correct.
Replace with correct size capacitor.
Run capacitor open, shorted or blown
Cause Solution
Wrong run capacitor
Excessive high-line voltage (110% of rated mix)
Replace with correct size capacitor.
Determine reason and correct.

Delay defective, burned out, or fails to close (PSC type motor only)

Cause Solution
Wrong relay
Wrong mounting angle
Line voltage too high or too low
Excessive short-cycling
Wrong run capacitor
Relay influenced by loose, vibrating mounting
Check and replace with correct relay.
Remount relay correctly.
Determine reason and correct.
Determine reason and correct.
Replace with correct size capacitor.
Remount rigidly.

High system pressure

Cause Solution
Compressor too small (if it's on suction side)
Inadequate external cooling of condensing unit

System overcharged
Air in system
Check size of compressor and replace.
Check air or water-cooling of condensation unit; remove restriction to flow. 
Check system requirements; adjust charge accordingly. Replace capillary tube or strainer.

Low System Pressure

Cause Solution
System undercharged

Restriction in capillary tube.
Repair leaks in system, if needed. Check system charge requirements and adjust accordingly. 
Replace capillary tube or strainer.

Space temperature too high

Cause Solution
Control setting too high
Partial restriction in capillary tube or strainer
Cooling coils too small
Inadequate air circulation
Reset control.
Replace capillary tube or strainer.
Add surface or replace with larger coils.
Improve air movement.

Suction line frosted or sweating

Cause Solution
System undercharged
Evaporator fan not running
System overcharged
Repair leaks, if needed, charge system.
Determine reason and correct.
Check system requirements; adjust charge accordingly.

Liquid line frosted

Cause Solution
Restriction in liquid line dryer or strainer
Liquid shut-off valve partially closed
Replace dryer or strainer.
Open valve fully.

Noisy System

Cause Solution
Loose parts or mountings
Tubing rattle
Bent fan blade causing vibration
Fan motor bearings
Locate loose areas and tighten.
Move tubing so it is not in contact with other parts. Replace blade.
Replace motor.

MORE Maintenance Tips for Room Air-Conditioners

A window-installed room air-conditioner has all the same components you'd find in a central system, but they're scaled down to fit into a two-section enclosure. The unit's smaller inside cell includes a blower, evaporator coil, and thermostat sensor that reads the temperature of air coming into the evaporator coil. The thermostat is located behind the control panel. A removable front panel covers everything and often holds the filter as well.

An isolation panel separates the components that are inside and those that are outside the window. The panel may have a shutter you adjust from the control panel to bring in outside air.

In the outside portion of the unit, a fan moves air through a condenser coil, where the refrigerant is liquefied and sent to the evaporator coil.

Most room air-conditioners are permanently lubricated. Routine upkeep consists of keeping the filters and coils clean. When a unit refuses to run, make sure its filter is clean and that the power cord is plugged in. Check the main service panel for a blown fuse or tripped circuit breaker. Don't restart a room air-conditioner for five minutes after it kicks off, to allow built-up heat to dissipate first.

If the unit cycles on or off too often or otherwise runs erratically, suspect thermostat problems. Often this means that the thermostat sensor has been knocked out of position. The sensor should be near the coil, but not touching it. Adjust it by carefully bending the wire. If you hear a gurgling noise, or if water drips from the front panel, shut off the power and use a level to make sure the cabinets outer section slopes toward its condensate drain.

Maintenance Tips

Some types of filters can be vacuumed; others should be washed or replaced. Clean or change the filter every two to three weeks.

Every month, check the condenser coil and intake vents for obstructions, such as leaves or dirt. Hose out this part of the unit every spring.

Also, check the condensate drain outlet. If it is plugged up or the unit is not properly pitched away from the house, condensation can't run out.



View Apartments  |   Students  |   Montreal City Information  |   Short-Term Stay  |   FREE RENT Contest  |   Client Login  |   Contact  |   Employment Opportunities  |   Testimonials  |   Home  |   Site Map
Legal Notice   |   Privacy Policy © 2008 Federal Real Estate. All rights reserved.
 
Click on your flag
to translate this page